Schneider / Sourcing catalogue
Schneider A9D19816 iC60H RCBO 16A 30m earth leakage circuit breaker 110v B19
In stock
At a glance
- Manufacturer
- Schneider
£129.99
Shipping and any applicable taxes are calculated at checkout.
View cart
Product details
Schneider A9D19816 iC60H 16 A RCBO

At a glance
| Condition | New |
|---|---|
| Stock reference | B19 |
| Manufacturer / MPN | Schneider Electric / A9D19816 |
| EAN | 3606480558313 |
| Current / curve | 16 A / C curve |
| Leakage protection | 30 mA / Type A |
| Rated voltage | 110/130 V AC, 50/60 Hz |
| Configuration | 1P + Ns; one protected pole |
| Breaking capacity | 10 kA Icn at 110 V AC |
| Dimensions | 110 H × 18 W × 77.5 D mm |
| Origin | Thailand, actual carton |
Select the exact A9D19816 110/130 V version for a compatible TN earthing system and distribution board. Check the manufacturer’s earthing restrictions before installation.
Product details
Schneider Electric Acti9 iC60H A9D19816 RCBO combines overload, short-circuit and residual-current protection. The actual carton identifies a C16, 30 mA Type A device, marked 110 V and Made in Thailand. EAN: 3606480558313.
Technical details
Rated 16 A at 50°C, with C-curve thermal-magnetic operation, instantaneous 30 mA Type A leakage response and voltage-dependent residual-current tripping. Manufacturer configuration: 1P + Ns, one protected pole, neutral on the left. Rated operational voltage 110/130 V AC at 50/60 Hz; breaking capacity 10 kA Icn and service capacity 7.5 kA Ics at 110 V AC.
Clip-on DIN-rail mounting; screw terminals; contact-position indication; IP20 device rating. Catalogue dimensions: 110 mm high × 18 mm wide × 77.5 mm deep; net weight 205 g. Operating range -15°C to +60°C. Confirm enclosure, busbar, conductor and terminal compatibility against the exact manufacturer instructions.
Condition and supplied item
One A9D19816 per purchase. Listed as new; the photographed carton has visible scuffing and worn edges. Only the carton is shown, so the internal unit, accessories and factory-seal condition are not independently visible. No test or commissioning result is claimed.
Installation and safety
Installation and testing are for a competent electrician. Isolate and prove dead before work. Schneider specifies TN earthing for this reference; its installation sheet excludes systems requiring double-pole switching, including IT or TT. Ensure all protected equipment is effectively earthed, disconnect the RCBO before dielectric testing and keep its neutral lead straight. Follow the attached HRB11380-01 instruction sheet. It specifies a maximum earthing resistance of 50 Ω for the 110 V device and testing each device monthly using the T button, subject to applicable local requirements. If it does not disconnect the supply during the test, seek expert advice. The test button is not an operating OFF switch.
New listing; actual labelled carton photographed. Review its storage wear and verify the internal unit and accessories before installation.
Request a quote
Enquire about this part
This product is included automatically. Tell us the quantity and any specific requirements.
Schneider A9D19816 iC60H RCBO 16A 30m earth leakage circuit breaker 110v B19
Manufacturer, warranty and firmware disclaimer
Independent supplier. Oakmore Global is an independent supplier. Unless expressly stated otherwise, we are not an authorised distributor, authorised surplus dealer or affiliate of the manufacturer. Manufacturer names, trade marks and part numbers are used for identification only and remain the property of their respective owners. No endorsement is implied. This notice applies to all manufacturers and brands listed on this website.
Product condition. Condition is as stated in the individual listing or our written quotation. Surplus, used or discontinued products may have older date codes, packaging, series or revisions than current factory stock. Please tell us about any required series, revision or compatibility before ordering.
Manufacturer warranty and support. Manufacturer warranties, technical support and software access may be unavailable or non-transferable. Oakmore Global does not promise a manufacturer's warranty unless expressly confirmed in the listing or quotation. Any warranty expressly offered by Oakmore Global is separate from the manufacturer's warranty.
Firmware, software and licensing. Unless expressly confirmed in the listing or quotation, we make no representation that a product includes firmware or software, or that any installed version meets your requirements. Purchase does not itself guarantee a software or firmware licence, licence transfer, download access, updates or manufacturer support. You are responsible for obtaining any required permissions and complying with the applicable end-user licence agreement and other licence terms before downloading, installing or using software or firmware. Oakmore Global will not separately source, download or supply firmware on your behalf.
Your rights. Nothing in this notice limits rights that cannot lawfully be excluded, changes our published returns policy, or overrides express commitments in the product listing or quotation.